Xantrex MS2000 Manual de usuario Pagina 93

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 126
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 92
Troubleshooting
975-0125-02-01 411
F7 Too many AC loads.
Turn some off, clear
fault, try again.
Escalating
Auto Fault.
Must occur
3 times in
30 seconds
before
becoming
a manual
fault.
AC Overload (PEAK
CURRENT) Shutdown
(AC OUTPUT)
Clear the fault and attempt
restart. Reduce AC loads.
F8 has lost input neutral
connection. See
guide.
Manual Neutral loss shutdown Clear the fault and attempt
restart. Check AC input wiring
for presence of a proper neutral
connection and ground
connection. Check the AC
input source to make sure the
neutral is bonded to ground.
F9 Battery voltage is too
high. See guide.
Automatic DC Over Voltage
Shutdown
Clear the fault and attempt
restart. Ensure battery voltage
is 1016 VDC at MS2000
terminals. Check all other
charging source outputs,
battery cables.
F10 Battery is too low,
cant invert.
Recharge battery.
Automatic DC Under Voltage
Shutdown (Immediate)
occurs if DC voltage is
below 8 volts DC
Clear the fault and attempt
restart. Recharge batteries.
Check battery cable
connections.
F11 Battery is too low,
cant invert.
Recharge battery.
Automatic DC Under Voltage
Shutdown occurs if
DC voltage is below
10 volts DC.
Clear the fault and attempt
restart. Recharge batteries.
Check battery cable
connections.
F12 Input AC too high.
Check source, clear
fault, try again.
Automatic AC Over Voltage
Shutdown (AC Line 1
input)
Clear the fault and attempt
restart. Check AC input
voltage. Check and adjust AC
input high voltage settings.
F13 Input AC too low.
Check source, clear
fault, try again.
Automatic AC Under Voltage
Shutdown (AC Line 1
input)
Clear the fault and attempt
restart. Check AC input
voltage. Check and adjust AC
input low voltage setting.
F14 Input AC too high.
Check source, clear
fault, try again.
Automatic AC Over Voltage
Shutdown (AC Line 2
input)
Not applicable for MS2000
Table 4-4
Fault Messages
Vista de pagina 92
1 2 ... 88 89 90 91 92 93 94 95 96 97 98 ... 125 126

Comentarios a estos manuales

Sin comentarios