Installation
2–20 975-0082-01-01
Type 11
Type 11 is a two-wire run mode configuration intended for Kohler
generators. It requires only two wires and one relay to control the
generator. Relay 1 closes momentarily once to start the generator, and
closes momentarily again to stop the generator.
The wiring diagram for a Type 11 configuration is the same as a two-wire
Type 7 configuration. See Figure 2-8.
Table 2-12
Type 11 relay and timing preset configurations
Relay 1 mode
MomentaryRun
Relay 3 mode
No function
Gen Run signal hold time
0.5 s
Preheat time
0 s
Preheat to crank delay
0 s
Crank time
10 s
Crank retry time
15 s
Shutdown bypass time
0 s
Start tries
3