Xantrex Automatic Generator Manual de usuario Pagina 112

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 124
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 111
Relay Timing
C–6 975-0082-01-01
The Auto Gen Start will make three attempts to stop the generator. If
the generator has still not stopped at the end of the third attempt, the
appropriate Fault will be generated.
Each stop attempt will consist of engaging the stop relay for 5 seconds
and then waiting 20 seconds before checking the state of the Gen Run
Signal to see if the stop attempt was successful.
Figure C-5
PulseStop mode timing diagram
Figure C-6
PulseStop mode Relay 1 behavior
Stop
Start
Time
Preheat
Relay1: Stop
Relay2: Start (Cranking)
Relay3: Preheat (Glow)
& Shutdown Bypass
Crank
Shutdown
Bypass
Vista de pagina 111
1 2 ... 107 108 109 110 111 112 113 114 115 116 117 ... 123 124

Comentarios a estos manuales

Sin comentarios